Curing-oven PLC and HMI updates

Sector
Manufacturing equipment
Region
Florida
The problem
A curing oven was shutting down on a high discharge-temperature condition during heat-up, before closed-loop PID control took over.
What Liquid did
Liquid updated the PLC and HMI: revised temperature-alarm logic, added a dedicated discharge-temperature safety parameter, and programmed a multi-stage blower sequence so heat-up is stable before PID control begins.
Result
Trials at lower curing temperatures confirmed the intended behavior.

Drive-shutdown investigation after a VFD upgrade

Sector
Food and beverage plant
Region
Florida
The problem
A process drive began shutting down at random after its variable-frequency drive was replaced.
What Liquid did
Liquid connected to the PLC, reviewed HMI alarm history and drive communication settings, compared control words between the previous and new ABB drives, and inspected the proximity switches used for speed measurement.
Result
Worn proximity switches were identified and recommended for replacement.

Batching and CIP upgrades

Sector
Food and beverage plant
Region
Midwest
The problem
The plant needed CIP improvements on a batching system, including PLC and HMI changes, so CIP could be started and run reliably from the CIP station.
What Liquid did
Liquid updated the batching and CIP PLC programs and HMI screens, added a one-command CIP start for an aseptic tank, corrected blend-tank sequence logic, fixed an HMI-to-PLC alarm-acknowledgement fault, and repaired CIP reporting in the HMI and SQL reports. Work was staged around production.
Result
The updated CIP sequences were commissioned and run on the plant's CIP circuits. A later visit corrected alarm acknowledgement and CIP reporting.

Chemical-dosing upgrade and Ignition SCADA

Sector
Dairy plant
Region
Western United States
The problem
The plant was upgrading chemical dosing on an aseptic processing line and needed PLC, HMI and SCADA changes to match the new equipment.
What Liquid did
Liquid reviewed P&IDs, updated the PLC and HMI programs, added HMI screens and alarms, corrected data-type and scaling issues, and updated the Ignition SCADA overview and P&ID screens for the new dosing selection.
Result
After dosing tests, the line completed CIP and sterilization and returned to production.

Health assessment of aseptic processing lines

Sector
Dairy plant
Region
Northeast
The problem
The plant asked for a health assessment of its aseptic processing lines after instrumentation, HMI and control issues on running equipment.
What Liquid did
Liquid spent a week on site assessing the lines, restored a pressure-transmitter signal that was not being logged, retuned PID loops to reduce process oscillations, corrected HMI tag errors, replaced a faulty conductivity transmitter, and corrected step logic that had been holding a sterilization step longer than required.
Result
The assessment was delivered with a follow-up action plan. Several control and instrumentation issues were corrected on site.

Commissioning support for an aseptic process expansion

Sector
Dairy plant
Region
Midwest
The problem
The plant was bringing an expanded aseptic processing area into production and needed on-site automation support during CIP, sterilization and production trials.
What Liquid did
Liquid supported CIP and SIP, diagnosed a CIP temperature shortfall caused by a failed valve solenoid, replaced the solenoid and re-ran CIP, helped resolve leaks found during sterilization, and identified an HMI limitation that made a held CIP phase look the same as a running phase.
Result
Production trials were completed with CIP and SIP support in place.

Integrating a process unit with a plant CIP platform

Sector
Dairy plant
Region
Mid-Atlantic
The problem
The plant needed a process unit integrated with a site CIP platform so CIP could run from the shared system.
What Liquid did
Liquid designed and tested new CIP sequence logic, staged the work around production, and coordinated a changeover method between the existing and new CIP systems.
Result
The new sequence logic was tested on site.

On-site production support for running process lines

Sector
Food and beverage plant
Region
South Central United States
The problem
The plant needed an embedded automation engineer on site to support running lines, sterilization sequences and planned maintenance.
What Liquid did
Liquid provided on-site production support, corrected PLC logic that was blocking valve activation during a sterilization cooling step, and troubleshot a sterilization temperature problem so the line could reach sterile water.
Result
The cooling-sequence logic was corrected and the line reached sterile water.
Does Liquid Consulting name its customers on this page?

No. Liquid withholds customer and plant names for confidentiality, and publishes named case studies only with the customer's written sign-off.

What kinds of project work does Liquid show here?

These summaries cover recent PLC, HMI and SCADA work, CIP and process upgrades, commissioning, assessments and on-site engineering support at food and beverage, dairy and other manufacturing plants in the United States.

Can Liquid work on running production lines?

Yes. Liquid stages automation work around production and shutdown windows, and supports plants during commissioning, assessments and ongoing production.

How do I start a project with Liquid?

Start with a 30-minute discovery call, usually followed by an Assessment & Roadmap: a 1–3 day site review that produces a system inventory, risk register, prioritized backlog and execution plan.

To start a project, begin with a 30-minute discovery call, usually followed by an Assessment & Roadmap: a 1–3 day site review that produces a system inventory, risk register, prioritized backlog and execution plan. Email automation@liquidconsulting.com or use the form below.

Talk To An
Automation Engineer

Tell us your site and the systems you want reviewed.